Free Subscription Submit Product & News Releases Today's News Headlines News By Company News By Date e-Newsletter Archives
Featured Suppliers Automation Product Manufacturers Systems Integrators and Service Providers Machine and Equipment Manufacturers
Product Search Featured Products Products by Category Products by Manufacturer Request Product Catalogs Submit Products
Add Event Hannover Messe 2012 Industrial Automation North America 2012
Employer Login Search for Jobs Post a Job 30-Day Job Posting Information Annual Job Slot Information Testimonials Recruiting Services Contract Services Salary Survey Results 2011
Techie Lounge Multimedia Library White Papers Training & Seminars Application Tools Complimentary Reference Guides Complimentary Evaluation Software Industry Web Sites Free Subscriptions to Trade Publications
LinkedIn Group Facebook Group Twitter YouTube Channel
Bookstore Online Training Courses Supplier Listings Automation.com Logo Items
 


 

Electrical & Control Panels Portal

  • Feedback
  • Print Page
An Introduction to K-Rated Transformers
 
Go to company's web site


January 19, 2011 - In recent years there has been an increasing awareness of the issue of power harmonics, stirred by the proliferation of sensitive electronics, high-powered computers, and more sophisticated equipment deployed in the industrial environment.

In an electrical power system, harmonics are current and voltage with frequencies that are integer multiples of the fundamental power frequency. That is, in a power system with a fundamental frequency of 60Hz, the second harmonic is 120Hz, the third harmonic is 180Hz, et cetera. Harmonics have no useful purpose, yet contribute to losses and lower system efficiency. Harmonics return over the neutral and are dissipated as heat in cables and load devices.

Transformers serving nonlinear loads have increased winding temperatures due to harmonic currents generated by those loads. This overheating likely will result in a shortened service life for the transformer. For example, operating a transformer at 10 degrees C above its insulation-rated class will cause approximately a 50% reduction in the life of the transformer. If the over temperature gets high enough or lasts long enough, the transformer will prematurely fail. Other warning signs of harmonics include: overheated neutral conductors and panels, unexplained tripping of circuit breakers, line voltage distortion, equipment failure, electrical fires, control equipment mis-operation, and interference on communication lines.

The "K-Factor" conveys a transformer's ability to serve varying degrees of nonlinear loads without exceeding the rated temperature rise limits. For any given nonlinear load, if the harmonic current components are known, the K-Factor can be calculated and compared to the transformer's nameplate K-Factor. As long as the load K-Factor is equal to or less than the transformer's rated K-Factor, the transformer does not need to be derated. The higher the K-Factor, the more non-linear loads the transformer can handle. The actual formula to determine K-Factor takes into account the frequency and current intensity of each individual harmonic. The chart below portrays typical load K-Factors.

K-Factor rated transformers are preferred over oversized (derated) conventional transformers because they are designed to supply nonlinear loads, are equipped with 200% rated neutral bus, and are likely to be smaller and less expensive. Disadvantages of an over-sized standard transformer may include the requirement for a higher short-circuit rating on circuit breakers and the drawing of a higher inrush current. Derating a standard transformer is only a temporary fix that often translates into lower efficiency operation.



ABOUT SolaHD
SolaHD specializes in identifying and providing industrial power quality solutions including power supplies, transformers and uninterruptible power systems. It is part of Emerson Industrial Automation and is headquartered in Rosemont, IL.
 