Introduction
Commercial
controllers such as the PID series (proportional, integral, derivative, and
their combinations) are linear devices within their normal operating range,
i.e., within set limits of input and output signals. Yet most fluid processes
which they are assigned to control are nonlinear to some degree, which means
that their gain in response to control action is subject to change. In this case
the controller cannot be optimally tuned except at one specific operating
condition. When the process load or controller set point change, the tuning
parameters may no longer provide the optimum recovery from disturbances. In some
cases, the process gain can even vary with the magnitude of the disturbance or
the deviation of the controlled variable from set point.
If the
variation in process gain is less than about 50 percent over the full operating
range, the response penalty will not be severe. However, the controller should
be tuned at the operating point where the gain is highest, so that the loop will
be stable at all times. For some loops, the gain variation is much greater than
this, in which case the controller gain is much lower than optimum at normal
production conditions, substantially compromising its performance. Two examples
are given here where the gain variation was sufficient to cause control
problems, and was corrected by applying characterization.
Locating
the Nonlinearity
Most
nonlinear behavior is associated with the final elementthe control valve. Its
characteristic is often incorrectly chosen. But when the pressure drop across
the valve is variablewhich is commonly the casenone of the standard valve
characteristics will deliver flow linearly with controller output. Furthermore,
some processes such as liquid-liquid heat exchangers do not transfer heat in a
linear relationship with fluid flow, in which case temperature is not linear
with flow.
When
the process nonlinearity is related to flow or process load, the loop gain will
be different for each value of load, and therefore with each value of controller
output. This is manifested as variable damping as a function of controller
output. The loop could be lightly damped at high values of controller output, or
at low values, depending on the shape of the nonlinear relationship. Quite
often, the highest process gain occurs at startup or standby conditions,
requiring the controller to be tuned there for stability; then it will not be
sufficiently responsive at normal production conditions.
It is
also possible for the nonlinear behavior to be associated with the controlled
variable, but this is far less common. The two applications most frequently
encountered are flow and pH loops. Nonlinear flow measurements are those where
head or differential pressure across a restriction is transmitted to the
controller. Modern dp transmitters and digital controllers can extract the
square root of the measured head, linearizing the flow signal for orifices and
nozzles; similar calculations can be made to linearize flow signals from flumes
and weirs.
With pH
measurements, however, the problem is more complex. The relationship between
reagent delivery and pH is logarithmic, capable of producing a gain variation
over several orders of magnitude. And it is not a simple relationshipthe
shape of a curve is a function of the ionic species in solution and their
concentrations. Each process may have its own characteristic curve, and even a
family of curves, changing with time. Measurement of oxidation-reduction
potential and ionic species other than hydrogen follow similar relationships.
If the
variable process gain is associated with the controller output, then a curve
characterizer applied to the controller output signal can correct the problem,
by essentially modifying the valve characteristic. For the head flowmeters
described above, characterization was applied to the flow measurement.
Similarly, for pH loops, characterization needs to be applied to the measurement
(and to the set point).
A
typical titration curve for industrial wastewater is shown in Fig. 1. The curve
is produced by titrating a sample with caustic in a laboratory, or by
incrementally raising the dosage

of
caustic delivered to the plant neutralization vessel under constant load (a far
slower and less-reliable procedure). The set point for the pH controller is
usually positioned in the region of neutrality, where the curve has its steepest
slopefor this curve, the maximum slope is 75 for a pH range of 2-12.
Consequently, the controller gain must be adjusted for stability there, to avoid
limit-cycling, a constant-amplitude cycling which can substantially increase
reagent consumption.

Figure
2 describes the simulated response of a pH control loop based on the titration
curve of Fig. 1 (without nonlinear compensation), following a step decrease in
acid load to the neutralization vessel. The vessel is simulated as being
well-mixed, and having a residence time of 20 minutes. The set point (SP) is
positioned at pH 7. Although the PI controller is tuned for light damping at set
point, as observed toward the end of the response, recovery of the process
variable (PV) from the upset is very slow, and is followed by a large overshoot.
Note that the controller output (CO) moves very slowly toward its new steady
state, because the controller gain is very low (0.167). For smaller load
changes, the response will be better, and for larger upsets, it will be worse.

The
loop can be linearized by placing a complementary nonlinear function in the path
of the pH measurement and set pointthat function is shown in Fig. 3. In
essence, this characterizer converts pH values into equivalent concentration of
caustic in solution, linear with the delivery of caustic by the controller.

Figure
4 repeats the step change in acid load with the characterizer applied to the
controller. The recovery is much quicker and damping uniformobserve that the
trajectory of the controller output is representative of a linear loop. The
integrated error between PV and SP has been reduced by a factor of two and the
integrated absolute error by almost a factor of three by the addition of the
characterizer. The controller gain has been increased to 7.7, but the loop is
now more heavily damped than before, and settles much more quickly.
Many
other possible curves existsome asymmetrical , as well as the possibility
that the set point may be positioned somewhere other than in the center of the
curve. For best results, the characterizer should match the titration curve as
accurately as possible. This requires at least ten points on an X-Y plot,
uniformly distributed over the operating pH range (not the reagent range). If
the curve happens to be variable, then the characterizer should be matched to
the most nonlinear curve.
Compressor
Control
Most
compressors are fitted with a recirculation valve, allowing some of the
compressed gas to be returned to the suction (after cooling) to control the
capacity of the machine over a wide flow range. Either the suction or discharge
pressure is controlled at the compressor, and the other pressure controlled
elsewhere or open to the atmosphere. The recirculation valve then typically
operates under constant pressure drop, in which case recycled flow is linear
with valve opening. The valve should therefore have a linear characteristic.

In many
compressor installations, however, an equal-percentage valve has been
incorrectly provided1. The gain of this valve varies directly with
the flow through it, as shown in Fig. 5. (Note that the valve is reverse-acting,
so that it will open on a signal failure.) Under no-load conditions, the valve
must recycle all the compressed flow, in which case it will approach full
opening, where its gain is highest. The pressure controller must be tuned for
stability here. As the load increases toward the normal production conditions,
the controller will close the valve accordingly, to a point where its gain will
be much lower and therefore the response to upsets will be sluggish.

The
response of a reciprocating compressor to a series of step load changes is
simulated in Fig. 6, with a linear and an equal-percentage recirculation valve
compared. As the load is stepped from zero to 80 percent, the pressure transient
with the linear valve remains essentially the same. However, with the
equal-percentage valve, the pressure controller had to be tuned at zero load,
where the valve gain is highest. Subsequent steps at higher loads show
progressively deteriorating response, owing to a reduction in loop gain.

A
linear recirculation valve should therefore be installed with each compressor.
However, in the event that an equal-percentage valve is already in place, the
incorrect characteristic can be corrected by inserting a complementary
characterizer in the controller-output path. The curve required to linearize the
valve of Fig. 5 appears in Fig. 7. Observe that the valve curve is simply
rotated 90 degrees to produce the characterizer.
Fine
Points
If the
equal-percentage valve were direct-acting, the characterizer curve would have to
bend in the other direction, i.e., lying above the diagonal. However, the
characterizer should always have a positive gain, so that the controller action
remains the same whether a characterizer is installed or not. The same is true
for pH characterizers. If the titration curve of Fig. 1 were reversed, for
example, by titrating a basic wastewater with an acid reagent, the same
characterizer would be used as that shown in Fig. 2.
Remember
that retuning of the controller is always required after installing a
characterizer, and always in the direction of raising its gain. The gain of the
pressure controller in the simulation with the linear valve is over three times
as high as with the equal-percentage valve. Therefore control will always be
tighter after the characterizer is installed than before.
References
Shinskey,
F. G., "Smoothing Out Compressor Control," Chem. Eng., Feb.
1999, pp. 127-130.
This
article was written by F. G. Shinskey and provided by Expertune. Expertune
designs pre-packaged industrial software which maximizes productivity and
efficiency and reduces waste in the process industries: chemical, pulp and
paper, utilities, refining, and food processing. For more information on
Expertune, please visit their website at: www.expertune.com.
(c)
copyright 1999-2003 ExperTune Inc.