DIN Rail Loop-Powered 4-20mA Signal Isolator

  • June 04, 2014
  • Shenzhen WAYJUN Industrial Automation
DIN Rail Loop-Powered 4-20mA Signal Isolator
DIN Rail Loop-Powered 4-20mA Signal Isolator

 

Features: >>Current loop power supply >>High linearity (0.2% F.S.) >>3000VDC isolation(4-20mA input/output) >>Frequency response(signal bandwidth): 50Hz(Io=20mA) >>Operating temperature range: -45~85deg.C >>Standard DIN35 rail mounting(size:69.5x79.0x25.0mm) >>Loop power supply:10-30V

Application:

>>PLC,DCS analog signal isolation,collecting

>>4-20mA signal isolation and transmission

>>Ground isolation and interference suppression

>>Signal long-term distortion-free transmission

>>Instrument signal transceiver and control

>>Power control, medical equipment isolation barrier

 

Product Listing:

Type No.

Input

Power supply

Output

DIN11-IAP100LF

4-20ma

No

4-20ma

 

 

 

 

Products Absolute Maximum Ratings:

Continuous isolation voltage: 3000VDC

Maximum input voltage: 32V

Operating temperature: +85 ‚ÑÉ

Storage temperature: +85 ‚ÑÉ

Output short circuit time: Sustainable

Note: Exceeding the maximum ratings may cause irreparable damage

 

 

 

 

 

 

 

 

 

 

 

General Parameter:

Parameter

Condition

MIN.

TYP.

MAX.

Unit

Isolation

1min

 

3000

 

VDC

Insulation resistance

 

 

10¹²‚Äñ1

 

Ω‚ÄñPf

Leakage Current

240Vrms,50Hz

 

0.5

 

uA

Temperature Drift

-45~+85‚ÑÉ

 

±50

±100

PPm/‚ÑÉ

Nonlinearity

 

 

±0.2

±0.2

%FSK

Input Voltage Range

 

8

 

32

V

Output Linear Range

 

0.03

4

20

mA

Output Current ( Io )

 

0.03

 

40

mA

Input Voltage Drop-out  ( Voh )

Io=20mA

 

 

4

V

Output Ripple

 

 

5

 

mV

Frequency response(signal bandwidth)

Io=20mA

 

50

 

Hz

Note: All specifications measured at TA=25°C, humidity<75%, nominal input voltage and rated output load unless otherwise specified.

 