• ISA provides technical resources and standards to help industrial automation professionals advance their careers and the field. We enable automation professionals worldwide to solve problems and enhance their skills by bringing people together to create new technologies and share best practices with future automation professionals.
    • Industry Insights

  • We attract over 140,000 unique automation professionals monthly, making us the premier online content provider and the only dedicated electronic magazine in the automation industry.

    Monthly Magazine

    • More things to read

    Back
    Back
  • M logo for Automation.com Monthly. Link to current issue.

AutoQuiz: Tuning the Temperature Controller for an Exothermic Reactor

By: Joel Don
09 December, 2016
1 min read
AutoQuiz: Tuning the Temperature Controller for an Exothermic Reactor
AutoQuiz: Tuning the Temperature Controller for an Exothermic Reactor
The temperature controller for an exothermic reactor must stay in automatic to prevent a runaway reaction.

AutoQuiz is edited by Joel Don, ISA's social media community manager.

Today's automation industry quiz question comes from the ISA Certified Automation Professional certification program . ISA CAP certification provides a non-biased, third-party, objective assessment and confirmation of an automation professional's skills. The CAP exam is focused on direction, definition, design, development/application, deployment, documentation, and support of systems, software, and equipment used in control systems, manufacturing information systems, systems integration, and operational consulting. Click this link for information about the CAP program. The following question comes from the CAP study guide, Performance Domain V, Deployment.

autoquiz-20161209-tuning-the-temperature-controller-for-an-exothermic-reactor

If an exothermic reactor can runaway in manual, then the temperature controller should be tuned with a(n):

a) open loop short cut method b) closed loop c) lambda tuning method d) reaction curve method e) none of the above

The controller must stay in automatic to prevent a runaway reaction. Closed-loop methods keep the controller in automatic. Normally, we maximize the gain to the point where either the error is small enough or the process starts to show a slight oscillation. It does not imply the ultimate oscillation method. The controller is in manual for open loop , lambda tuning , and reaction curve methods.

The best answer is B , closed loop.

Reference

: Greg McMillan, Good Tuning: A Pocket Guide .