• ISA provides technical resources and standards to help industrial automation professionals advance their careers and the field. We enable automation professionals worldwide to solve problems and enhance their skills by bringing people together to create new technologies and share best practices with future automation professionals.
    • Industry Insights

  • We attract over 140,000 unique automation professionals monthly, making us the premier online content provider and the only dedicated electronic magazine in the automation industry.

    Monthly Magazine

    • More things to read

    Back
    Back
  • M logo for Automation.com Monthly. Link to current issue.

AD Converters Quiz: convert an analog signal to a digital one

By: Mark Weisner
03 November, 2011
1 min read
AD Converters Quiz: convert an analog signal to a digital one

AD Converters are necessary to convert an analog signal to a digital one that our computers can understand. The output of an AD Converter is a binary number. Digital instruments most commonly use 12, 14 and 16-bit converters, although there are much higher bit converters available.

The following is a practice question from one of ISA’s classes:

1. Calculate the incremental steps for a 12-bit A/D converter

2. If the sensor connected to the A/D converter was ranged for 0-1000 F, what is the smallest increment of temperature that can be seen on the digital side of the A/D converter?

3. If I wanted to control the temperature to within 0.1 F can I do this with a 12-bit A/D converter in the sensor module?

4. What effect would a 14-bit A/D have?

5. Can you think of further improvements?

  • Answer to 1.

LSB represents = 100% / 2^12 = 100%/4096 = 0.0244%

  • Answer to 2.

LSB (or smallest increment of temperature on the digital side):

= 1000 F / 2^12 = 1000 F/ 4096 = 0.244 F

  • A 12-bit A/D converter in the sensor module is not accurate enough.
  • A 14-bit A/D converter would give a resolution or LSB of :
  • = 1000  F / 2^14 = 1000  F / 16384 = 0.061  F
  • 14-bit A/D converter would be better for control to within 0.1 F, however a 16-bit A/D converter would be even better because the resolution would be 0.0153 F.

Some points to remember are that although a higher bit converter allows for highly accurate instruments, we want our test equipment that we use to calibrate them to be at least 4 times more accurate. So for example if we had a transmitter with an accuracy of .02% FS, then our test equipment would have to have an accuracy of .005% FS. Also if the AD Converter on the host system’s analog input card (when the transmitter’s digital signal is being converted to 4-20) is not equal or higher in bits then the transmitter’s, the resolution that you gained is lost.