Mass Flow Meter Summary
The ST50 Series Flow Meters are an accurate, easy to install, no moving parts mass flow meter solution. Model ST50 is used for compressed air and nitrogen flow. Model ST51 is used for measuring biogas, digester gas, methane and natural gas. The ST50 Series utilizes FCI proven thermal dispersion technology to provide direct mass flow measurement resulting in higher performance at a lower cost than orifice plates, DP, Vortex shedding and other thermal devices. The meter installs in line sizes ranging from 2 to 24 inches [51 to 610mm] with 1/2" or 3/4" NPT.
The ST50 Series uses precision, lithography structured platinum RTD sensors embedded in FCI's equal mass small diameter, all metal thermowells. Combined with microprocessor electronics and precision calibration, the ST50 achieves excellent accuracy, fast response and virtually maintenance free operation.
Model ST50 Applications
- Wastewater Treatment Aeration Control
- Blower and Dryer Air Flow Control
- Burner and Furnace Air Flow Control
- Lake, Pond and Aquaculture Aeration
- HVAC Duct/Damper Control
- Compressed Air Distribution Measurements
Model ST51 Applications
Specifications
Pipe/Line Size Compatibility:2" to 24" [51 mm to 610 mm]Flow Rate:ST50:0.75 to 400 sfps [0.23 to 122 mps]ST51:0.3 to 400 sfps [0.08 to 122 mps]Accuracy:(at calibrated conditions)Standard:± 2% reading, ± 0.5% full scale Optional:± 1% reading, ± 0.5% full scale Temperature Coefficient:(at calibrated conditions) With optional extended temperature compensation. Valid from 10% to 100% of full-scale calibration Flow: Maximum ± 0.025% of reading/ºF up to 250ºF [±0.05% of reading/ºC up to 121 ºC] Repeatability:± 0.5% readingTemperature Compensation:Standard:40° to 100° F [4° to 38° C];Optional:0° to 250° F [-18° to 121° C]Turndown Ratio:10:1 to 100:1Flow ElementInstallation: InsertionType:Thermal DispersionMaterial of Construction:316 stainless steel body with Hastelloy C thermowell sensors, 316 stainless steel compression fitting with teflon or stainless steel ferrule. Pressure (Maximum Operating without Damage):Stainless steel ferrule: 500 psig [34 bar(g)] Teflon ferrule: 150 psig [10 bar(g)] Operating Temperature:Stainless steel ferrule: 0° to 250° F [-18° to 121° C] Teflon ferrule: 0° to 200° F [-18° to 93° C] Process Connection:1/2" MNPT or 3/4" MNPT with stainless steel or Teflon ferrule. Insertion Length(Field Adjustable) 1: 1 to 6 inches [25 to 152 mm] 1 to 12 inches [25 to 305 mm] 1 to 18 inches [25 to 457 mm] Flow TransmitterEnclosure:NEMA4X (IP67) aluminum, Epoxy coated Operating Temperature:0° to 140° F [-18° to 60° C]Input Power:DC:18 to 36 Vdc AC:85 to 265 Vac (CE Mark Approval from 100 to 240 Vac). Communication Port:RS-232C, Wireless IR to PDA with optional digital display models Installation:Integral or Remote (50'[15m] max.) |